SMALL COMMERCIAL SYSTEMS 5KW TO 10KW - 3Ф

Rotosol Invert offers modular design three phase inverters for small commercial systems.
This design improves the generation efficiency and system stability
thereby reducing cost of installation and maintenance.

product image
ELECTRICAL SPECIFICATION RIT5K RIT6K RIT8K RIT10K

INPUT(DC)

Max DC Power (W) 5500 6600 8800 11000
Max DC Voltage (V) 1000 1000 1000 1000
Rated / Recommended Voltage WI 620 620 620 620
MPPT DC Voltage Range (V) 200-800 200-800 250-800 300-800
Start up DC Voltage (V) 250 250 320 320
Max DC Current (A) 11*2 11*2 11*2 11*2
Number of MPPT Tracker 2 2 2 2
Number of DC Connections (set) 2 2 2 2

OUTPUT(AC)

Max AC Power (W) 5350 6450 8600 10000
Nominal AC Power (W) 5000 6000 8000 10000
Max AC Current (A) 8.5 10.5 13.5 17
Nominal AC Current (A) 7 8.5 11 14
Nominal AC Voltage (V) 3P+N+PE/3P+PE, 230/400
Nominal AC Frequency (Hz) 50/60
Power Factor -0.95 ~ +0.95
Output current THD <3%

Power consumption

Power consumption at Night (W) <1
Power consumption at Standby (W) 10

Power Efficiency

Max Efficiency 98.10% 98.10% 98.20% 98.20%
Euro Efficiency 97.55% 97.60% 97.65% 97.70%
MPPT Efficiency 99.90% 99.90% 99.90% 99.90%

Safety and protection

Safety Standard EN/IEC 62109-1/-2
EMC Standard EN/IEC 61000-6, EN61000-3
Anti-islanding Protection Internal

General information

Dimensions (W*H*D) (mm) 680*345*170
Enclosure IP65
RCD Internal
Weight (kg) 21.5
Ambient Temperature Range -25°C ~ +60°C
Relative humidity 0%~100%
Topology Transformerless
Communication Interface RS485 / WIFI / Wired Ethernet / GPRS (Optional)
Cooling Concept Convection
Noise Emission (dB) <40
Maximum Altitude (above sea level) (m) Up to 2000m without derating
Top